Thursday, October 20, 2011

Aspects of Protection system

Reliability
  • Dependability - protection should operate when it should operate
  • Security - protection should not operate when it should not operate
Speed
We need fast protection to minimize the damage

Selectivity/Discrimination
Zones of protections are determined by the CTs
Understand the type of the fault and fault location

Cost
Cost/beneficial analysis
fast operation and duplication require additional cost
Back up protection

ANSI reference numbers
21 - Distance relay
50 - Instantaneous over current
51 - time delayed over current
52 - circuit breaker
67 - Directional over current
87 - Differential

Faults in power systems

There are two categories of faults:

  • Active Faults : Current flow from one phase to another or phase to ground. Two sub categories solid faults(complete breakdown of insulation) and incipient faults(faults start from very small beginning).
  • Passive Faults : These are not real faults, but stressing the system to its maximum capacity, and ultimately active fault occurs. (Overloading, over voltage, under frequency and power swings)

Transient Faults : do not damage the insulation permanently and allow the system to re energized after a short time period (lightning strike, momentary tree contact)
Permanent faults : does not disappear when the power is disconnected. equipment has to be repaired.

Symmetrical faults are balanced faults. Sinusoidal are equal about their axis. represent steady state operation.
Asymmetrical faults displays a dc offset and become a symmetrical fault after some time

Wednesday, October 19, 2011

Availability of hardware in substations

The software and hardware in the substation are designed in a way that they meet high availability requirements. The means high reliability ( Long mean-time-to fail MTTF) and short down time ( Short mean-time-to recover MTTR). MTTF means statistical time until component need a repair.Short down times can be achieved by extensive diagnostic functions, modular hardware designs, fast reconfiguration and automatic restart after a power supply failure.

The redundancy recomended:
  • Repair faulty parts in process and bay level in less than two hours and less than 4 h for station level.
  • Standby hardware exist physically connected and per-configured.
  • Warm standby - standby HW constantly supervise active HW, automatically takes over in a failure. Time stamped events may be lost. commands are reusable after 10-30 sec
  • Host standby -  standby HW constantly supervise active HW, it takes over in a failure. No Time stamped events  lost. commands are reusable after 1-5 sec. at bay level switch over time is less than 100ms.
Self supervision of IEDs
  • Insensitive against EMI
  • A/D conversion may subjected to aging should be supervised by a reference signal
  • Watchdog should supervise the response time from processing algorithms
  • Checksums are used detect failure in mamory
  • Loss of power should be checked
Supervision of communication:
  • All communication devices ( Star couplers, routers, switches) are subjected to self supervision
  • Detection of errors, check the response time and counting lost messages






    Communication requirements of Substation Automation architecture

    Introduction of microprocessors in to substation allows process data in digital form. to convert analog data in to digital ADCs are used. These digital data is not distorted due to aging of the hardware and can easily exchanged  by serial communication. But these serial communication introduces additional delays.Also information processing hardware must withstand harsh environment in the substation, specially EMI.
    The data is acquired at the process level by means of remote i/o units (RIO) and intelligent sensors (PISA = process interface for sensors and actuators). The process bus connects them to the bay level equipments.

    Communication requirements:
    Maximum allowed age - worse case response time can be tolerated. This means, that this time must be guaranteed in normal operation.
    Data integrity - degree of communication safety in the case of disturbances. If data is directly influence the process those data has higher integrity.
    Exchange method - Spontaneous mean communicated as soon as it happens. Request means communicated on request by some function or human.

    Alarm - 1s - Medium - Spontaneous
    Commands - 1s - High - Spontaneous
    Process sate data -2s (binary) 5-10s (measured) - Medium - Spontaneous (gives overview of the process state)
    Time stamped events - 10s - low - On request (used for later analysis)
    Interlocking data - 5ms - high - Spontaneous (used to prevent dangerous commands)
    Interlocking data (state info) - 100ms - high - On request
    Trip from protection - 3ms - high - Spontaneous (used to clear faults)

    The actual communication throughput capacity must be higher than needed for normal operation( at least 10% higher). When we design the communication system we should avoid the single point of failure.
    No communication message failure shall lead to a unsafe action. This can be tackled using communication error detection mechanisms and making transmission media immune to disturbances( reduce number of bit errors). Today all process buses are typically a Hamming distance of at least 4 - 6, to detect transmission errors. This is sufficient for medium integrity. In substation error rate is higher than the telecommunication environment. There for we use glass fiber in the process bus and special communication procedures like "select before use" is introduced.
    No lost or late message is allowed to lead to unsafe action.Messages could be lost due to buffer overflows or overloaded routers and switches. There for lost messages and loss of message source should be detected. In IEC 61850 topical flag is used to indicate data is up to date.Glass fiber can cover a distance up to 2000m with out loosing transmission speed. while plastic fiber is used for shorter length( tenth of meters). Also plastic fiber is aging sooner than glass.

    Today we can place the microprocessor based relays close to the process. In new architecture physical signal marshaling is replaced by logical signal marshaling, which means complexity is the same. Electrical CAD systems are replaced by signal engineering tools.

    For redundancy we duplicate the protection devices at least in HV substations.
    To provide passive safety in logical nodes it sends at least two telegrams before a command is executed. This two step approach is called select before approach (SBO). HMI send the select command to CBC node. Then CBC sends selected command back to HMI. Then only HMI sends the operate command to the exact switch.

    Substation Automation Structure

    Business benifits of substation automation are :
    • Better information, Higher productivity
    • Intelligent automation, Higher productivity and higher availability

    Substation automation structure include Station level, Bay level and process level.

    Station Level provides Remote communication to Network control center (NCC) ,HMI, Station level automation, data evaluation and archiving, condition monitoring, events and alarms, station level protection and  Data exchange. Station level equipments are always separated in to two rooms - operation room and the communication equipment room.
    Bay Level provides bay level automation, time synchronization, condition monitoring, bay level protection, bay level control, object protection and data acquisition.

    Process Level includes GIS or AIS switchgear, instrument transformers, power transformers and surge arresters.Output of VT (100v or 200v) and CTs (1 or 5A)

    Time synchronization has two general approches;
    Separate synchronization pulse - separate wire for all the IEDs
    Using communication buses- master clock broadcast time telegrams and slaves regularly ask for time

    Tuesday, August 9, 2011

    RTU and Substation automation

    Remote Terminal Unit (RTU) lies between the substation and the network controlling center(NCC). Basically RTU interfaces the devices in the physical world to the SCADA. An RTU can be interfaced with the Central Station with different communication media (usually serial (RS232, RS485, RS422) or Ethernet). RTU can support standard protocols (Modbus, IEC 60870-5-101/103/104, DNP3, ICCP, etc.) to interface any third party software. 

    Saturday, August 6, 2011

    Common Data classes

    IEC 61850-7-3 defines common data classes for a wide range of well known applications. The
    core common data classes are classified into the following groups:

    – status information,
    – measurand information
    – controllable status information,
    – controllable analogue information,
    – status settings,
    – analogue settings
    – description information.

    There are services to exchange these data.The services defined in IEC 61850-7-2 are called abstract services.

    The four main building blocks of the Substation Automation System


    • the substation automation system specific information models(logical nodes and data)
    • the information exchange methods(interface)
    • the mapping to concrete communication protocols, (mapping to MMS and TCP/IP)
    • the configuration of a substation IED.

    Sunday, July 10, 2011

    Why Power needs montoring

    Power can not store like water and gas. So power has to generate according to the demand. Power generation sense the load demand by falling frequency. We can not always direct power in a specific path, because current always follows the path of least resistance. This means power transmission and distribution has to be monitor and control through out the day. Smart grid is the solution for the most of the problem in the power control and motoring. From power generation to the power consumption transformers steps voltage up and down to efficiently deliver power to the customer. Mainly electric grid consist of power genration, power transmission and power distribution. Substations transforms voltage from high to low or reverse. Electrical power may flow through several substations form power generation plant to the consumer.

    Network security for Substation automation systems

    Power system reliability has achieved higher priority in equipment implementation in the power industry over the years. Power industry has paid more attention on the information structure that supports the monitoring and controlling the power system after the August 14, 2003 black out. Initial power equipment problem in 2003 blackout, on-going and cascading failures were due to problems in providing right information to the right place within the right time.

    Communication protocols are one of the most critical parts of power system operations, responsible for communication between equipment and controlling them. Theses protocols rarely incorporated any security measures since these protocols were very specialized. “Security by Obscurity” has been the primary approach because only operators are allowed to control breakers from highly protected control center. With the increasing electricity market force security by obscurity is no longer a valid concept. Because the electricity market is pressuring market participants to gain any edge they can, it is all about winning bids and loosing bids. Also the older communications protocols are being replaced by standardized, well-documented protocols that are more susceptible to hackers and other security breaches.  Since power systems failure has greater scope and cost, it is obvious that the security in the power system is crucial factor.

    Now there are two infrastructures to be managed in the power systems, one is power system infrastructure and the other is information infrastructure. With saying that we can see any unreliability in the information infrastructure can cause the power system unreliable. So the information system has to ensure its reliability level to provide the required reliability level in the power system.

    The International Electrotechnical Commission (IEC) Technical Council (TC) 57 Power Systems Management and Associated Information Exchange is responsible for developing international standards for power system data communications protocols. IEC TC57 has developed three widely accepted protocols, and has been the source for the IEC 61850. Those three protocols are IEC 60870-5, DNP 3.0 and IEC 60870-6.

    IEC 61850 protocol security


    IEC61850 is an Ethernet (IEEE 802.3) based communication protocol used for control and automation of electric substations using microprocessor based Intelligent Electronic Devices (IED’s). It was developed jointly by the IEC (International Electrotechnical Commission) and the IEEE with the aim of providing a flexible and interpretable communication system which could be easily integrated into the infrastructure of existing substations.

    IEC61850 is a protocol used for control and automation of substations. In substation automated by IEC 61850, the IED’s communicate via this protocol. An IED could be any measuring instrument which has a microprocessor such as a current transformer or voltage transformer or a protection device such as a relay. They are communicating peer to peer, broadcast messages and as client server. For an example if the current transformer detect over current in the line it broadcast the value to protective devices to act accordingly.
    IED network within a substation contain two main busses. 

    They are namely process bus and the station bus.
    • Process Bus -Transfers unprocessed power system information to the processing IED’s
    • Station Bus - integrates all process buses together and provides the interface to external networks. Human Machine Interfaces (HMI) are connected to the station bus.

    IEC61850 has been designed considering the security aspects of the communication. The existing security mechanisms of IEC61850 are mentioned in IEC62351-4 and IEC62351-6.
    These include:

    • IEC62351-4 specifies the ciphers used by IEC61850 for encryption. In addition, IEC62351-6 specifies the use of Transport Layer Security (TLS).
    • Security for IEC61850 profiles using VLAN’s. Partitioning of the network into VLAN’s prevent unauthorized access of IED’s outside the designated VLAN.
    • Security for Simple Network Time Protocol (SNTP) via the mandatory use of the authentication algorithms of RFC2030. This prevents tampering via false time stamp packets.
    • Explicit countering of man-in-the-middle attacks and tampering using the Message Authentication Code (MAC) of IEC62351-6.
    • Explicit countering of replay attacks via the specialized processing state machines mentioned in IEC62351-4.
    IEC 62351 - Data and communication security
    IEC has published a standard for data and communication security in power systems as IEC 62351, wich includes parts 1 to 7.

    ·         IEC 62351-1: Data and Communication Security – Introduction
    ·         IEC 62351-2: Data and Communication Security – Glossary of Terms
    ·         IEC 62351-3: Data and Communication Security – Profiles Including TCP/IP
    ·         IEC 62351-4: Data and Communication Security – Profiles Including MMS
    ·         IEC 62351-5: Data and Communication Security – Security for IEC 60870-5 and Derivatives (i.e. DNP 3.0)
    ·         IEC 62351-6: Data and Communication Security – Security for IEC 61850 Profiles
    ·         IEC 62351-7: Data and Communication Security – Security Through Network and System Management


    IEC 61850 profiles that run over TCP/IP will use IEC 62351-3, in which the primary security measures are IPSec and TLS. It specifies the use of Transport layer security (TLS) which is commonly used over the Internet for secure interactions, covering authentication, confidentiality, and integrity. IEC 62351-4 provides security for profiles that include the Manufacturing Message Specification (MMS) with TLS.

    IEC 61850 also contains three protocols (GOOSE, GSE, and SMV) that are multicast datagrams and not routable, designed to run on a substation LAN or other non-routed network. The main protocol, GOOSE, is designed for protective relaying where the messages need to be transmitted within 4 milliseconds peer-to-peer between intelligent controllers. Encryption or other security measure which will affect the transmission rate is not acceptable here. So authentication is the only security measure acceptable and IEC 62351-6 provides mechanism where theses profiles can digitally sign the messages.

    IEC 62351 Part 5 relates to the specialties of serial communication. Here, additional security measures are defined to especially protect the integrity of the connections. This part also specifies the key management necessary for the security measures. IEC 62351 Part 7 describes security related data objects for end-to-end network and system management (NSM) and also security problem detection. These data objects support the secure control of dedicated parts of the energy automation network. IEC 62351 Part 8 addresses the integration of role-based access control mechanisms into the whole domain of power systems.

    Security in power system operation

    Security requirements of power systems are different from the other industries. As an instance internet environment is vastly different form the power system environment. So it is critical to have a better understanding of the security requirements and the potential impact of the security measures on the communication requirements of the power system operations.

    Security services have been developed for industries that do not have strict performance and high reliability requirements as power industries do.

    • Denial of service has far more impact in the power industry than many typical internet transactions. Preventing authorized dispatcher form accessing the power system substation control has serious consequences than preventing a customer form accessing his bank account.
    • Communication channels used in power system are narrow band which permitting the overhead needed for encryption and key exchange.
    • In power system industries some substations and equipments are located in unmanned remote areas which makes lot of security measures are difficult to implementation
    • Wireless communication are becoming used for many applications but have to be more careful in implementing in power system because the noisy electrical environment in the power substations.

     Power system security uses large variety of communication methods and performance characteristics, single security measure cannot counter all the security threats.  For instance VPNs only secure the transport level protocols, so we need additional security measures to protect the application level protocols.  In power system communication authentication plays a larger role in many security measures, because authentication of control actions is far more important than the data through encryption. Security truly is an “end-to-end” requirement to ensure authenticated access to sensitive power system equipment, reliable and timely information on equipment functioning and failures, backup of critical systems, and audit capabilities that permit reconstruction of crucial events.

    GOOSE/SMV protection

    GOOSE is stand for Generic Object Orientated System-wide Events. By using GOOSE with station bus communication, aims to replace the conventional hardwired logic necessary for intra-relay coordination. When IED detect an event it multicast values to notify devices which have registered to receive the data. Because this information is time critical, performance requirements are stringent. In the GOOSE communication no more than 4ms is allowed to elapse from the time an event occur to the time of message transmission.   In order to replace the conventional method of using contacts and wires, the performance of the GOOSE messaging, i.e. transfer time should be less than 3ms for a Trip GOOSE command and 20ms for a Block GOOSE command as specified in IEC 61850-5 'Communication requirements for functions and device models’. The amount of data that would be generated after the event is based on the network topology IEDs follow, number of IEDs in the network and the type of the event. We can see that in this scenario collision are quite possible, so the GOOSE messages are retransmitted multiple times by each IED.  GOOSE model groups data value in to data sets to be published. In peer to peer data value publishing GOOSE model has several attributes that can be used to control the publishing process.

    GOOSE messaging is a very important in multi vendor interoperability. The purpose and the advantages of GOOSE:
    • Only a single LAN cable/fibre is required instead of connecting conventional metallic wiring between protection devices or between protection devices and primary equipment. This reduces the total cost involve in building a system in substation.
    • Multi vendor interoperability, Connection between IEDs provided by different vendors is much easier to achieve
    • Modification or addition of data communications between IEDs can be easily achieved by the re-configuration of the IEDs’ GOOSE settings, rather than by complex metallic wiring.
    Virtual LAN vulnerabilities
    In the power industry they use VLAN for layer2 security. Virtual LAN (VLAN) technology is used to create logically separate LANs on the same physical switch. Each port of the switch is assigned to a VLAN.
    VLAN is not secure enough for GOOSE and SMV messages. VLAN has security vulnerabilities and only VLAN implementation is not enough for GOOSE/SMV communication. VLAN switch implementations have been susceptible to a variety of Denial of Service attacks, including traffic flooding, MAC flooding and CAM table poisoning (CAM refers to the Content Addressable Memory used to list MAC addresses reachable through each switch port).
    VLAN switch configurations and deployments have been vulnerable to a number of spoofing and man-in-the-middle attacks. The most well known exploits include the following. (Links at the end of this article lead to detailed descriptions.)

    • MAC address spoofing
    • VLAN tag spoofing (where the attack computer falsely identifies itself as a member of a VLAN by spoofing the IEEE 802.1q tag )
    • ARP cache poisoning
    • Connection hijacking following a successful ARP attack
    •  Multicast Brute Force Attack
    •  Random Frame Stress Attack
    •  Private VLAN Attack
    Power industry has paid more attention on the information structure that supports the monitoring and controlling the power system. Communication protocols are one of the most critical parts of power system operations, responsible for communication between equipment and controlling them. IEC61850 protocol which is used for control and automation of substations has been designed considering the security aspects of the communication. The existing security mechanisms of IEC61850 are mentioned in IEC62351 standard. Security requirements of power systems are different from the other industries. . In order to maintain security in power systems, constant vigilance and monitoring are needed as well as adaptation to changes in the overall power system. The main purpose of the security protection is to detect the attack and eliminate it form the system. Power system security uses large variety of communication methods and performance characteristics, single security measure cannot counter all the security threats.  In IEC 61850 there are mainly five message types used for communication sample measured values, GOOSE, MMS, GSSE and time sync. There are four types of information exchange methods. They are Client/server services, GOOSE/GSE Management Services, GSSE Services and Time Sync exchange. IEC 61850 profiles that run over TCP/IP will use security measures IPSec and Transport layer security (TLS).Client server and the GSSE information exchange which uses MMS are using network layer and transport layer security measures to achieve secure combination. With stringent performance requirement in GOOSE and SMV message communication, encryption or other security measures which may significantly affect transmission rates are not acceptable. Therefore, authentication is the primary security measure for GOOSE and SMV. VLAN has security vulnerabilities and VLAN implementation alone is not enough for GOOSE/SMV communication. We should research on the better authentication which matches to the substation communication requirements and we can implement that authentication value as an extension to the GOOSE message.